OpenStudio Results
Model Summary
| Information | Value | Units |
|---|---|---|
| Building Name | NECB 2011-SmallHotel-NECB HDD Method-CAN_MB_Brandon.711400_CWEC.epw created: 2017-06-30 16:29:07 +0000 | building_name |
| Net Site Energy | 3,240,890 | kBtu |
| Total Building Area | 43,202 | ft^2 |
| EUI (Based on Net Site Energy and Total Building Area) | 75.02 | kBtu/ft^2 |
| OpenStudio Standards Building Type | SmallHotel |
| Value | |
|---|---|
| Weather File | Brandon MB CAN WYEC2-e-14997 WMO#=711400 |
| Latitude | 49.92 |
| Longitude | -100.0 |
| Elevation | 1342 (ft) |
| Time Zone | -6.0 |
| North Axis Angle | 180.00 |
| ASHRAE Climate Zone |
| Maximum Dry Bulb (F) | Daily Temperature Range (R) | Humidity Value | Humidity Type | Wind Speed (mph) | Wind Direction | |
|---|---|---|---|---|---|---|
| BRANDON ANN CLG .4% CONDNS DB=>MWB | 87.08 | 22.5 | 68.18 | Wetbulb [F] | 11.41 | 180.0 |
| BRANDON ANN CLG .4% CONDNS WB=>MDB | 82.22 | 22.5 | 71.6 | Wetbulb [F] | 11.41 | 180.0 |
| BRANDON ANN HTG 99.6% CONDNS DB | -28.3 | 0.0 | -28.3 | Wetbulb [F] | 9.17 | 280.0 |
| Time Setpoint Not Met | Time (hr) |
|---|---|
| During Heating | 41.5 |
| During Cooling | 3.0 |
| During Occupied Heating | 36.5 |
| During Occupied Cooling | 3.0 |
| Tolerance for Time Setpoint Not Met | Temperature (F) |
|---|---|
| Heating | 1.8 |
| Cooling | 1.8 |
Annual Overview
One or more tables in Annual Overview section returned false and was skipped.
| End Use | Consumption (kBtu) |
|---|---|
| Heating | 1,500,006 |
| Cooling | 73,598 |
| Interior Lighting | 372,615 |
| Exterior Lighting | 0 |
| Interior Equipment | 93,379 |
| Exterior Equipment | 0 |
| Fans | 173,327 |
| Pumps | 2,540 |
| Heat Rejection | 133 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 1,025,292 |
| Refrigeration | 0 |
| Generators | 0 |
| Fuel | Consumption (kBtu) |
|---|---|
| Electricity | 3,240,890 |
| Natural Gas | 0 |
| Additional Fuel | 0 |
| District Cooling | 0 |
| District Heating | 0 |
| End Use | Consumption (kWh) |
|---|---|
| Heating | 439,608 |
| Cooling | 21,569 |
| Interior Lighting | 109,203 |
| Exterior Lighting | 0 |
| Interior Equipment | 27,367 |
| Exterior Equipment | 0 |
| Fans | 50,797 |
| Pumps | 744 |
| Heat Rejection | 39 |
| Humidification | 0 |
| Heat Recovery | 0 |
| Water Systems | 300,483 |
| Refrigeration | 0 |
| Generators | 0 |
Monthly Overview
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | Total | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 89470.0 | 70311.39 | 57150.0 | 27049.64 | 12563.03 | 5116.14 | 2788.75 | 3921.36 | 11862.72 | 24930.61 | 51816.94 | 82626.94 | 439607.53 |
| Cooling | 12.83 | 15.5 | 23.55 | 391.72 | 1449.98 | 4455.81 | 7139.69 | 5917.22 | 1534.63 | 593.57 | 20.62 | 13.63 | 21568.75 |
| Interior Lighting | 9274.53 | 8378.94 | 9308.33 | 8924.72 | 9308.33 | 8998.53 | 9234.53 | 9308.33 | 8958.56 | 9274.53 | 8998.53 | 9234.53 | 109202.39 |
| Exterior Lighting | |||||||||||||
| Interior Equipment | 2324.35 | 2099.92 | 2335.12 | 2232.89 | 2335.12 | 2256.72 | 2311.29 | 2335.12 | 2243.66 | 2324.35 | 2256.72 | 2311.29 | 27366.55 |
| Exterior Equipment | |||||||||||||
| Fans | 3863.44 | 3490.92 | 3866.89 | 3876.92 | 4299.64 | 4871.78 | 5436.14 | 5187.5 | 4219.19 | 4081.97 | 3741.83 | 3861.11 | 50797.33 |
| Pumps | 22.41 | 19.66 | 19.23 | 36.55 | 93.94 | 120.53 | 129.0 | 128.11 | 84.58 | 49.56 | 18.49 | 22.17 | 744.21 |
| Heat Rejection | 0.0 | 0.18 | 0.95 | 6.23 | 16.18 | 13.53 | 1.76 | 0.67 | 0.0 | 0.0 | 39.49 | ||
| Humidification | |||||||||||||
| Heat Recovery | |||||||||||||
| Water Systems | 27539.22 | 25344.47 | 28065.0 | 26488.92 | 26203.22 | 23986.69 | 23542.89 | 22921.14 | 22219.06 | 23684.47 | 24163.36 | 26325.53 | 300483.97 |
| Refrigeration | |||||||||||||
| Generators | |||||||||||||
| Total | 132506.78 | 109660.8 | 100768.12 | 69001.53 | 56254.2 | 49812.42 | 50598.47 | 49732.31 | 51124.16 | 64939.74 | 91016.5 | 124395.2 | 949810.22 |
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Heating | 245.3911 | 226.1763 | 174.1955 | 96.5149 | 60.0552 | 22.8054 | 47.8763 | 112.3637 | 186.6716 | 221.5821 | ||
| Cooling | 0.0153 | 0.0398 | 0.0527 | 2.1732 | 16.2178 | 18.5776 | 0.0487 | 0.0343 | 0.0106 | |||
| Interior Lighting | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 | 17.3704 |
| Exterior Lighting | ||||||||||||
| Interior Equipment | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 | 4.5171 |
| Exterior Equipment | ||||||||||||
| Fans | 5.3572 | 5.3572 | 5.3572 | 5.3572 | 5.374 | 6.2431 | 9.1635 | 8.9779 | 5.374 | 5.3572 | 5.3572 | 5.3572 |
| Pumps | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.0187 | 0.2386 | 0.2386 | 0.0187 | 0.0187 | 0.0187 | 0.0187 |
| Heat Rejection | 0.0343 | 0.0474 | ||||||||||
| Humidification | ||||||||||||
| Heat Recovery | ||||||||||||
| Water Systems | 75.0868 | 74.2879 | 75.5815 | 75.2589 | 72.4182 | 74.3188 | 72.9591 | 67.5347 | 56.5756 | 58.9474 | 69.9734 | 74.6554 |
| Refrigeration | ||||||||||||
| Generators | ||||||||||||
| Total | 347.74 | 327.73 | 277.06 | 199.08 | 159.81 | 127.45 | 120.5 | 117.26 | 131.78 | 198.61 | 283.92 | 323.5 |
Utility Bills/Rates
No Data to Show for Utility Bills/Rates
Envelope
| Construction | Net Area (ft^2) | Surface Count | R Value (ft^2*h*R/Btu) |
|---|---|---|---|
| Customized opaque construction {82417552-4e72-49a3-b58c-a7c931cda125} to conductance of 0.21 | 16,258 | 92 | 27.04 |
| Customized opaque construction {8cd40ce1-66fb-418c-8dd0-366012e9f042} to conductance of 0.162 | 10,800 | 16 | 35.05 |
| Construction | Area (ft^2) | Surface Count | U-Factor (Btu/ft^2*h*R) |
|---|---|---|---|
| Customized Fenestration: cond=0.220 tvis=0.220 tsol=0.232 | 1,983 | 103 | 0.3874 |
| Description | Total (%) | North (%) | East (%) | South (%) | West (%) |
|---|---|---|---|---|---|
| Gross Window-Wall Ratio | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Gross Window-Wall Ratio (Conditioned) | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
| Skylight-Roof Ratio | 0.0 |
Space Type Breakdown
| Space Type Name | Floor Area (ft^2) | Standards Building Type | Standards Space Type |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F | 5,670 | Space Function | Corr. >= 2.4m wide-sch-F |
| Space Function Electrical/Mechanical-sch-F | 1,215 | Space Function | Electrical/Mechanical-sch-F |
| Space Function Gym - fitness | 351 | Space Function | Gym - fitness |
| Space Function Hotel/Motel - lobby | 1,755 | Space Function | Hotel/Motel - lobby |
| Space Function Hway lodging - rooms | 27,271 | Space Function | Hway lodging - rooms |
| Space Function Lobby - elevator | 648 | Space Function | Lobby - elevator |
| Space Function Lounge/recreation | 351 | Space Function | Lounge/recreation |
| Space Function Office - enclosed | 1,404 | Space Function | Office - enclosed |
| Space Function Stairway-sch-F | 1,728 | Space Function | Stairway-sch-F |
| Space Function Storage area - occsens | 2,457 | Space Function | Storage area - occsens |
| Space Function Washroom-sch-F | 351 | Space Function | Washroom-sch-F |
Space Type Summary
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Corr. >= 2.4m wide-sch-F People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Lights Definition | 0.6596 | W/ft^2 | 1.0 |
| Space Function Corr. >= 2.4m wide-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Electrical/Mechanical-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Lights Definition | 1.2356 | W/ft^2 | 1.0 |
| Space Function Electrical/Mechanical-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Gym - fitness People Definition | 0.0186 | people/ft^2 | 1.0 |
| Space Function Gym - fitness Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Lights Definition | 0.9104 | W/ft^2 | 1.0 |
| Space Function Gym - fitness Ventilation (outdoor air method Sum) | 0.8600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hotel/Motel - lobby People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Lights Definition | 1.0591 | W/ft^2 | 1.0 |
| Space Function Hotel/Motel - lobby Ventilation (outdoor air method Sum) | 0.2850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Hway lodging - rooms People Definition | 0.0037 | people/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Elec Equip Definition | 0.2323 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Lights Definition | 0.7525 | W/ft^2 | 1.0 |
| Space Function Hway lodging - rooms Ventilation (outdoor air method Sum) | 0.1100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lobby - elevator People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lobby - elevator Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Lights Definition | 0.6410 | W/ft^2 | 1.0 |
| Space Function Lobby - elevator Ventilation (outdoor air method Sum) | 0.8100 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Lounge/recreation People Definition | 0.0093 | people/ft^2 | 1.0 |
| Space Function Lounge/recreation Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Lights Definition | 0.7860 | W/ft^2 | 1.0 |
| Space Function Lounge/recreation Ventilation (outdoor air method Sum) | 0.1850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Office - enclosed People Definition | 0.0046 | people/ft^2 | 1.0 |
| Space Function Office - enclosed Elec Equip Definition | 0.6968 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Lights Definition | 1.1055 | W/ft^2 | 1.0 |
| Space Function Office - enclosed Ventilation (outdoor air method Sum) | 0.0850 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Stairway-sch-F People Definition | 0.0005 | people/ft^2 | 1.0 |
| Space Function Stairway-sch-F Lights Definition | 0.6875 | W/ft^2 | 1.0 |
| Space Function Stairway-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Storage area - occsens People Definition | 0.0009 | people/ft^2 | 1.0 |
| Space Function Storage area - occsens Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Lights Definition | 0.5686 | W/ft^2 | 1.0 |
| Space Function Storage area - occsens Ventilation (outdoor air method Sum) | 0.0700 | cfm/floor area ft^2 |
| Definition | Value | Unit | Inst. Multiplier |
|---|---|---|---|
| Space Function Washroom-sch-F People Definition | 0.0031 | people/ft^2 | 1.0 |
| Space Function Washroom-sch-F Elec Equip Definition | 0.0929 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Lights Definition | 0.8779 | W/ft^2 | 1.0 |
| Space Function Washroom-sch-F Ventilation (outdoor air method Sum) | 0.0600 | cfm/floor area ft^2 |
Interior Lighting Summary
| Zone | Lighting Power Density (W/ft^2) | Total Power (W) | Schedule Name | Scheduled Hours/Week (hr) | Actual Load Hours/Week (hr) | Return Air Fraction | Annual Consumption (kWh) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.66 | 1068.58 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3180.56 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION CORR. >= 2.4M WIDE-SCH-F LIGHTS | SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.66 | 890.48 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2650.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 433.73 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 1291.67 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION ELECTRICAL/MECHANICAL-SCH-F LIGHTS | SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1.24 | 1067.63 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3177.78 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION GYM - FITNESS LIGHTS | SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.91 | 319.57 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1725.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN SPACE FUNCTION HOTEL/MOTEL - LOBBY LIGHTS | SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1.06 | 1858.83 | NECB-H-LIGHTING | 151.2 | 151.2 | 0.0000 | 14655.56 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 853.41 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 2541.67 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1056.6 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 264.15 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1056.52 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 3144.44 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN SPACE FUNCTION HWAY LODGING - ROOMS LIGHTS | SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 264.13 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 786.11 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN SPACE FUNCTION LOBBY - ELEVATOR LIGHTS | SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.64 | 103.85 | NECB-C-LIGHTING | 75.0 | 75.0 | 0.0000 | 405.56 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN SPACE FUNCTION LOUNGE/RECREATION LIGHTS | SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0.79 | 275.87 | NECB-B-LIGHTING | 103.58 | 103.57 | 0.0000 | 1488.89 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS | SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1.11 | 1552.17 | NECB-A-LIGHTING | 56.27 | 56.27 | 0.0000 | 4552.78 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.69 | 148.49 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN SPACE FUNCTION STAIRWAY-SCH-F LIGHTS | SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.69 | 148.53 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 441.67 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.57 | 76.76 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 219.44 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.57 | 598.7 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 1711.11 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN SPACE FUNCTION STORAGE AREA - OCCSENS LIGHTS | SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.57 | 122.85 | NECB-E-LIGHTING | 54.82 | 54.82 | 0.0000 | 350.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN SPACE FUNCTION WASHROOM-SCH-F LIGHTS | SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.88 | 308.17 | NECB-F-LIGHTING | 57.1 | 57.1 | 0.0000 | 916.67 |
Plug Loads Summary
| Electricity Annual Value (kWh) | |
|---|---|
| InteriorEquipment:Electricity:Zone:SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
| InteriorEquipment:Electricity:Zone:SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 238.89 |
| InteriorEquipment:Electricity:Zone:SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 3213.89 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 783.33 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 972.22 |
| InteriorEquipment:Electricity:Zone:SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 241.67 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 175.0 |
| InteriorEquipment:Electricity:Zone:SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3622.22 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 36.11 |
| InteriorEquipment:Electricity:Zone:SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 280.56 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 58.33 |
| InteriorEquipment:Electricity:Zone:SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 97.22 |
Exterior Lighting
No Data to Show for Exterior Lighting
Water Use Equipment
| Instance | Plant Loop | Definition | Space | Peak Flow Rate (gal/min) | Flow Rate Schedule | Target Temp Range (F) |
|---|---|---|---|---|---|---|
| Employeeloungeflr1 Service Water Use 0.02gal/min | Main Service Water Loop | Employeeloungeflr1 Service Water Use Def 0.02gal/min | EmployeeLoungeFlr1 | 0.02 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Exercisecenterflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Exercisecenterflr1 Service Water Use Def 0.05gal/min | ExerciseCenterFlr1 | 0.05 | NECB-B-Service Water Heating | 140.0 to 140.0 |
| Frontloungeflr1 Service Water Use 0.04gal/min | Main Service Water Loop | Frontloungeflr1 Service Water Use Def 0.04gal/min | FrontLoungeFlr1 | 0.04 | NECB-H-Service Water Heating | 140.0 to 140.0 |
| Frontofficeflr1 Service Water Use 0.05gal/min | Main Service Water Loop | Frontofficeflr1 Service Water Use Def 0.05gal/min | FrontOfficeFlr1 | 0.05 | NECB-A-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr1 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr1 Service Water Use Def 0.0gal/min | FrontStorageFlr1 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr2 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr2 Service Water Use Def 0.0gal/min | FrontStorageFlr2 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr3 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr3 Service Water Use Def 0.0gal/min | FrontStorageFlr3 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Frontstorageflr4 Service Water Use 0.0gal/min | Main Service Water Loop | Frontstorageflr4 Service Water Use Def 0.0gal/min | FrontStorageFlr4 | 0.00 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Guestroom101 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom101 Service Water Use Def 0.07gal/min | GuestRoom101 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom102 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom102 Service Water Use Def 0.07gal/min | GuestRoom102 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom103 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom103 Service Water Use Def 0.07gal/min | GuestRoom103 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom104 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom104 Service Water Use Def 0.07gal/min | GuestRoom104 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom105 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom105 Service Water Use Def 0.07gal/min | GuestRoom105 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom201 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom201 Service Water Use Def 0.07gal/min | GuestRoom201 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom202_205 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom202_205 Service Water Use Def 0.27gal/min | GuestRoom202_205 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom206_208 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom206_208 Service Water Use Def 0.22gal/min | GuestRoom206_208 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom209_212 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom209_212 Service Water Use Def 0.27gal/min | GuestRoom209_212 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom213 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom213 Service Water Use Def 0.07gal/min | GuestRoom213 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom214 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom214 Service Water Use Def 0.07gal/min | GuestRoom214 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom215_218 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom215_218 Service Water Use Def 0.27gal/min | GuestRoom215_218 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom219 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom219 Service Water Use Def 0.07gal/min | GuestRoom219 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom220_223 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom220_223 Service Water Use Def 0.27gal/min | GuestRoom220_223 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom224 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom224 Service Water Use Def 0.07gal/min | GuestRoom224 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom301 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom301 Service Water Use Def 0.07gal/min | GuestRoom301 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom302_305 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom302_305 Service Water Use Def 0.27gal/min | GuestRoom302_305 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom306_308 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom306_308 Service Water Use Def 0.22gal/min | GuestRoom306_308 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom309_312 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom309_312 Service Water Use Def 0.27gal/min | GuestRoom309_312 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom313 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom313 Service Water Use Def 0.07gal/min | GuestRoom313 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom314 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom314 Service Water Use Def 0.07gal/min | GuestRoom314 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom315_318 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom315_318 Service Water Use Def 0.27gal/min | GuestRoom315_318 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom319 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom319 Service Water Use Def 0.07gal/min | GuestRoom319 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom320_323 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom320_323 Service Water Use Def 0.27gal/min | GuestRoom320_323 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom324 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom324 Service Water Use Def 0.07gal/min | GuestRoom324 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom401 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom401 Service Water Use Def 0.07gal/min | GuestRoom401 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom402_405 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom402_405 Service Water Use Def 0.27gal/min | GuestRoom402_405 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom406_408 Service Water Use 0.22gal/min | Main Service Water Loop | Guestroom406_408 Service Water Use Def 0.22gal/min | GuestRoom406_408 | 0.22 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom409_412 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom409_412 Service Water Use Def 0.27gal/min | GuestRoom409_412 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom413 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom413 Service Water Use Def 0.07gal/min | GuestRoom413 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom414 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom414 Service Water Use Def 0.07gal/min | GuestRoom414 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom415_418 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom415_418 Service Water Use Def 0.27gal/min | GuestRoom415_418 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom419 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom419 Service Water Use Def 0.07gal/min | GuestRoom419 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom420_423 Service Water Use 0.27gal/min | Main Service Water Loop | Guestroom420_423 Service Water Use Def 0.27gal/min | GuestRoom420_423 | 0.27 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Guestroom424 Service Water Use 0.07gal/min | Main Service Water Loop | Guestroom424 Service Water Use Def 0.07gal/min | GuestRoom424 | 0.07 | NECB-F-Service Water Heating | 140.0 to 140.0 |
| Laundryroomflr1 Service Water Use 0.03gal/min | Main Service Water Loop | Laundryroomflr1 Service Water Use Def 0.03gal/min | LaundryRoomFlr1 | 0.03 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr1 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr1 Service Water Use Def 0.01gal/min | RearStorageFlr1 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr2 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr2 Service Water Use Def 0.01gal/min | RearStorageFlr2 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr3 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr3 Service Water Use Def 0.01gal/min | RearStorageFlr3 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
| Rearstorageflr4 Service Water Use 0.01gal/min | Main Service Water Loop | Rearstorageflr4 Service Water Use Def 0.01gal/min | RearStorageFlr4 | 0.01 | NECB-E-Service Water Heating | 140.0 to 140.0 |
HVAC Load Profiles
| Jan | Feb | Mar | Apr | May | Jun | Jul | Aug | Sep | Oct | Nov | Dec | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Average Outdoor Air Dry Bulb (F) | -0.4 | 5.5 | 19.4 | 38.6 | 52.4 | 61.0 | 65.7 | 64.0 | 52.4 | 40.9 | 22.6 | 4.6 |
| Cooling Load (MBtu) | 0.04 | 0.05 | 0.08 | 1.34 | 4.95 | 15.2 | 24.36 | 20.19 | 5.24 | 2.03 | 0.07 | 0.05 |
| Heating Load (MBtu) | 305.28 | 239.91 | 195.0 | 92.3 | 42.87 | 17.46 | 9.52 | 13.38 | 40.48 | 85.07 | 176.81 | 281.93 |
Zone Conditions
| Zone | Unmet Htg (hr) | Unmet Htg - Occ (hr) | < 56 (F) | 56-61 (F) | 61-66 (F) | 66-68 (F) | 68-70 (F) | 70-72 (F) | 72-74 (F) | 74-76 (F) | 76-78 (F) | 78-83 (F) | 83-88 (F) | >= 88 (F) | Unmet Clg (hr) | Unmet Clg - Occ (hr) | Mean Temp (F) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 242 | 542 | 501 | 3601 | 999 | 2875 | 0 | 0 | 0 | 0 | 0 | 0 | 72.3 (F) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 6 | 354 | 2897 | 1492 | 4011 | 0 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 20 | 467 | 3021 | 1350 | 3902 | 0 | 0 | 0 | 0 | 0 | 0 | 73.1 (F) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 589 | 424 | 396 | 3609 | 1131 | 2611 | 0 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2412 | 767 | 614 | 3651 | 449 | 851 | 15 | 1 | 0 | 0 | 0 | 0 | 69.5 (F) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2162 | 1152 | 494 | 3675 | 428 | 833 | 15 | 1 | 0 | 0 | 0 | 0 | 69.5 (F) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2185 | 1154 | 470 | 3674 | 427 | 834 | 15 | 1 | 0 | 0 | 0 | 0 | 69.5 (F) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 2940 | 690 | 276 | 3562 | 380 | 896 | 15 | 1 | 0 | 0 | 0 | 0 | 69.2 (F) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 711 | 672 | 469 | 3766 | 905 | 2225 | 12 | 0 | 0 | 0 | 0 | 0 | 71.6 (F) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 42 | 37 | 0 | 1 | 102 | 225 | 505 | 2223 | 2352 | 2907 | 431 | 14 | 0 | 0 | 3 | 3 | 72.9 (F) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 110 | 485 | 707 | 4326 | 814 | 2306 | 12 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 152 | 463 | 957 | 1571 | 1878 | 3410 | 329 | 0 | 0 | 0 | 0 | 0 | 72.7 (F) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 750 | 281 | 484 | 4084 | 676 | 2485 | 0 | 0 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 721 | 284 | 472 | 4055 | 654 | 2574 | 0 | 0 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 759 | 270 | 461 | 4069 | 638 | 2563 | 0 | 0 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 1056 | 309 | 313 | 4073 | 635 | 2374 | 0 | 0 | 0 | 0 | 0 | 0 | 71.5 (F) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 836 | 944 | 898 | 2241 | 1003 | 2441 | 397 | 0 | 0 | 0 | 0 | 0 | 71.5 (F) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 513 | 1110 | 893 | 2336 | 981 | 2454 | 473 | 0 | 0 | 0 | 0 | 0 | 71.7 (F) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 772 | 1013 | 806 | 2334 | 916 | 2372 | 538 | 9 | 0 | 0 | 0 | 0 | 71.6 (F) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1883 | 588 | 629 | 2246 | 816 | 2019 | 440 | 139 | 0 | 0 | 0 | 0 | 70.9 (F) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 88 | 511 | 2936 | 1502 | 3723 | 0 | 0 | 0 | 0 | 0 | 0 | 72.9 (F) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 99 | 516 | 2980 | 1439 | 3726 | 0 | 0 | 0 | 0 | 0 | 0 | 72.9 (F) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 7 | 217 | 646 | 3219 | 1336 | 3335 | 0 | 0 | 0 | 0 | 0 | 0 | 72.7 (F) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 63 | 409 | 1942 | 1939 | 4407 | 0 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 47 | 370 | 1724 | 1938 | 4681 | 0 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 126 | 315 | 476 | 3124 | 1165 | 3554 | 0 | 0 | 0 | 0 | 0 | 0 | 72.6 (F) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 50 | 332 | 2504 | 1403 | 4469 | 2 | 0 | 0 | 0 | 0 | 0 | 73.2 (F) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 80 | 414 | 2730 | 1341 | 4194 | 1 | 0 | 0 | 0 | 0 | 0 | 73.1 (F) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 60 | 374 | 2699 | 1397 | 4230 | 0 | 0 | 0 | 0 | 0 | 0 | 73.1 (F) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 0 | 116 | 604 | 3028 | 1267 | 3745 | 0 | 0 | 0 | 0 | 0 | 0 | 72.9 (F) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 17 | 244 | 1727 | 1806 | 4962 | 4 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 23 | 218 | 1555 | 1748 | 5211 | 5 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 44 | 383 | 1908 | 1946 | 4477 | 2 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 21 | 169 | 1326 | 1636 | 5603 | 5 | 0 | 0 | 0 | 0 | 0 | 73.8 (F) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 30 | 237 | 1598 | 1751 | 5140 | 4 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 249 | 356 | 443 | 3384 | 1061 | 3267 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 1 | 118 | 452 | 2759 | 1270 | 4159 | 1 | 0 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 9 | 149 | 488 | 2816 | 1231 | 4067 | 0 | 0 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 1 | 118 | 469 | 2814 | 1278 | 4080 | 0 | 0 | 0 | 0 | 0 | 0 | 73.0 (F) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 6 | 188 | 622 | 3100 | 1245 | 3599 | 0 | 0 | 0 | 0 | 0 | 0 | 72.7 (F) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 50 | 348 | 1910 | 1779 | 4672 | 1 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 45 | 265 | 1685 | 1630 | 5130 | 5 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 53 | 390 | 1986 | 1893 | 4436 | 2 | 0 | 0 | 0 | 0 | 0 | 73.3 (F) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 42 | 240 | 1656 | 1612 | 5205 | 5 | 0 | 0 | 0 | 0 | 0 | 73.6 (F) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 0 | 53 | 347 | 1915 | 1731 | 4710 | 4 | 0 | 0 | 0 | 0 | 0 | 73.4 (F) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0 | 0 | 0 | 0 | 837 | 375 | 326 | 3855 | 890 | 2477 | 0 | 0 | 0 | 0 | 0 | 0 | 71.6 (F) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 645 | 387 | 336 | 3552 | 984 | 2856 | 0 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 659 | 386 | 343 | 3539 | 963 | 2870 | 0 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 644 | 389 | 343 | 3554 | 978 | 2852 | 0 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 685 | 424 | 357 | 3695 | 907 | 2692 | 0 | 0 | 0 | 0 | 0 | 0 | 71.8 (F) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 539 | 394 | 361 | 3199 | 1147 | 3120 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 544 | 371 | 346 | 3055 | 1098 | 3346 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 546 | 420 | 419 | 3266 | 1242 | 2867 | 0 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 541 | 372 | 339 | 3055 | 1101 | 3352 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 544 | 399 | 352 | 3179 | 1095 | 3191 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0 | 0 | 0 | 0 | 1652 | 877 | 615 | 2259 | 1092 | 1921 | 272 | 72 | 0 | 0 | 0 | 0 | 70.8 (F) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 164 | 594 | 556 | 3722 | 955 | 2769 | 0 | 0 | 0 | 0 | 0 | 0 | 72.2 (F) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 550 | 504 | 393 | 3796 | 845 | 2672 | 0 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 395 | 398 | 460 | 4101 | 1063 | 2343 | 0 | 0 | 0 | 0 | 0 | 0 | 71.9 (F) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 329 | 363 | 461 | 3987 | 1046 | 2574 | 0 | 0 | 0 | 0 | 0 | 0 | 72.1 (F) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 404 | 382 | 434 | 4088 | 1004 | 2448 | 0 | 0 | 0 | 0 | 0 | 0 | 72.0 (F) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 930 | 378 | 367 | 4306 | 944 | 1835 | 0 | 0 | 0 | 0 | 0 | 0 | 71.3 (F) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 2122 | 452 | 663 | 2383 | 731 | 1810 | 549 | 50 | 0 | 0 | 0 | 0 | 70.6 (F) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 2123 | 425 | 650 | 2377 | 660 | 1879 | 565 | 81 | 0 | 0 | 0 | 0 | 70.7 (F) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 2174 | 447 | 609 | 2377 | 641 | 1819 | 570 | 123 | 0 | 0 | 0 | 0 | 70.7 (F) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0 | 0 | 0 | 0 | 2623 | 451 | 422 | 2326 | 672 | 1618 | 412 | 236 | 0 | 0 | 0 | 0 | 70.3 (F) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0 | 0 | 0 | 0 | 68 | 528 | 622 | 3655 | 925 | 2962 | 0 | 0 | 0 | 0 | 0 | 0 | 72.4 (F) |
| Zone | < 30 (%) | 30-35 (%) | 35-40 (%) | 40-45 (%) | 45-50 (%) | 50-55 (%) | 55-60 (%) | 60-65 (%) | 65-70 (%) | 70-75 (%) | 75-80 (%) | >= 80 (%) | Mean Relative Humidity (%) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 5598 | 752 | 636 | 729 | 681 | 276 | 88 | 0 | 0 | 0 | 0 | 0 | 24.0 (%) |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 5772 | 723 | 529 | 634 | 591 | 356 | 137 | 18 | 0 | 0 | 0 | 0 | 23.6 (%) |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 5762 | 717 | 528 | 628 | 602 | 376 | 132 | 15 | 0 | 0 | 0 | 0 | 23.7 (%) |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 5663 | 672 | 574 | 542 | 605 | 431 | 198 | 62 | 12 | 1 | 0 | 0 | 24.2 (%) |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 5233 | 613 | 547 | 462 | 424 | 450 | 479 | 291 | 171 | 79 | 11 | 0 | 26.9 (%) |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 5254 | 607 | 541 | 455 | 394 | 462 | 479 | 300 | 176 | 78 | 14 | 0 | 26.8 (%) |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 5253 | 604 | 543 | 452 | 398 | 460 | 483 | 299 | 174 | 80 | 14 | 0 | 26.9 (%) |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 5218 | 599 | 509 | 480 | 425 | 408 | 493 | 320 | 206 | 86 | 14 | 2 | 27.1 (%) |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 4711 | 751 | 760 | 629 | 635 | 600 | 466 | 165 | 39 | 3 | 1 | 0 | 29.7 (%) |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1967 | 748 | 755 | 940 | 960 | 1288 | 1180 | 501 | 250 | 85 | 74 | 12 | 43.2 (%) |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 4609 | 735 | 693 | 670 | 663 | 692 | 536 | 162 | 0 | 0 | 0 | 0 | 30.7 (%) |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 5128 | 730 | 694 | 1286 | 717 | 205 | 0 | 0 | 0 | 0 | 0 | 0 | 26.6 (%) |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 5672 | 681 | 573 | 578 | 656 | 392 | 156 | 51 | 1 | 0 | 0 | 0 | 23.8 (%) |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 5682 | 689 | 573 | 594 | 641 | 390 | 149 | 41 | 1 | 0 | 0 | 0 | 23.6 (%) |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 5678 | 690 | 588 | 597 | 639 | 387 | 142 | 37 | 2 | 0 | 0 | 0 | 23.6 (%) |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 5642 | 683 | 651 | 657 | 587 | 378 | 137 | 23 | 2 | 0 | 0 | 0 | 23.6 (%) |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 5411 | 823 | 616 | 647 | 625 | 330 | 185 | 60 | 48 | 15 | 0 | 0 | 25.5 (%) |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 5449 | 771 | 621 | 671 | 581 | 370 | 178 | 62 | 43 | 14 | 0 | 0 | 25.4 (%) |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 5449 | 766 | 627 | 669 | 607 | 355 | 178 | 58 | 38 | 13 | 0 | 0 | 25.4 (%) |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 5438 | 784 | 680 | 589 | 633 | 341 | 194 | 73 | 25 | 3 | 0 | 0 | 25.1 (%) |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 1831 | 1390 | 1144 | 1098 | 942 | 814 | 777 | 517 | 203 | 44 | 0 | 0 | 41.3 (%) |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 1826 | 1388 | 1142 | 1101 | 941 | 809 | 775 | 528 | 208 | 42 | 0 | 0 | 41.4 (%) |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 1776 | 1391 | 1109 | 1046 | 954 | 865 | 807 | 564 | 204 | 44 | 0 | 0 | 41.7 (%) |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 1952 | 1416 | 1203 | 1117 | 929 | 845 | 713 | 410 | 153 | 22 | 0 | 0 | 40.5 (%) |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 2010 | 1451 | 1224 | 1090 | 920 | 832 | 725 | 358 | 133 | 17 | 0 | 0 | 40.1 (%) |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 2995 | 1128 | 982 | 955 | 841 | 817 | 646 | 315 | 80 | 1 | 0 | 0 | 37.7 (%) |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2359 | 1410 | 1129 | 1102 | 872 | 814 | 617 | 353 | 103 | 1 | 0 | 0 | 39.1 (%) |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2329 | 1364 | 1122 | 1094 | 863 | 804 | 649 | 386 | 138 | 11 | 0 | 0 | 39.5 (%) |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2333 | 1368 | 1117 | 1088 | 840 | 790 | 652 | 403 | 149 | 20 | 0 | 0 | 39.5 (%) |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2274 | 1330 | 1075 | 1111 | 895 | 858 | 685 | 392 | 132 | 8 | 0 | 0 | 39.8 (%) |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 2472 | 1417 | 1211 | 1003 | 807 | 778 | 621 | 323 | 123 | 5 | 0 | 0 | 38.7 (%) |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 2509 | 1435 | 1193 | 976 | 775 | 763 | 626 | 347 | 127 | 9 | 0 | 0 | 38.7 (%) |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 2395 | 1394 | 1135 | 990 | 819 | 791 | 688 | 379 | 155 | 14 | 0 | 0 | 39.4 (%) |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 2588 | 1448 | 1211 | 976 | 736 | 747 | 603 | 318 | 127 | 6 | 0 | 0 | 38.4 (%) |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 2502 | 1443 | 1214 | 1024 | 785 | 770 | 625 | 291 | 103 | 3 | 0 | 0 | 38.5 (%) |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 3037 | 1094 | 917 | 926 | 818 | 800 | 670 | 361 | 128 | 9 | 0 | 0 | 37.9 (%) |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2358 | 1368 | 1113 | 1090 | 855 | 803 | 646 | 379 | 138 | 10 | 0 | 0 | 39.4 (%) |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2346 | 1347 | 1118 | 1096 | 866 | 806 | 656 | 378 | 137 | 10 | 0 | 0 | 39.4 (%) |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2352 | 1354 | 1111 | 1080 | 862 | 804 | 648 | 389 | 146 | 14 | 0 | 0 | 39.5 (%) |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2300 | 1307 | 1068 | 1092 | 896 | 868 | 713 | 386 | 122 | 8 | 0 | 0 | 39.7 (%) |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 2477 | 1384 | 1194 | 1010 | 831 | 784 | 645 | 317 | 112 | 6 | 0 | 0 | 38.8 (%) |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 2552 | 1434 | 1209 | 975 | 765 | 748 | 626 | 323 | 122 | 6 | 0 | 0 | 38.5 (%) |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 2451 | 1365 | 1153 | 965 | 809 | 784 | 681 | 379 | 156 | 17 | 0 | 0 | 39.2 (%) |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 2569 | 1438 | 1211 | 982 | 752 | 749 | 616 | 317 | 121 | 5 | 0 | 0 | 38.4 (%) |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 2484 | 1396 | 1226 | 1010 | 824 | 778 | 625 | 314 | 101 | 2 | 0 | 0 | 38.6 (%) |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 3567 | 905 | 853 | 813 | 766 | 720 | 649 | 318 | 140 | 28 | 1 | 0 | 36.0 (%) |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3224 | 1008 | 942 | 876 | 821 | 718 | 653 | 350 | 142 | 25 | 1 | 0 | 37.2 (%) |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3222 | 1006 | 938 | 891 | 825 | 718 | 647 | 348 | 137 | 27 | 1 | 0 | 37.2 (%) |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3224 | 1007 | 936 | 881 | 815 | 718 | 651 | 357 | 144 | 26 | 1 | 0 | 37.2 (%) |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3208 | 978 | 939 | 852 | 839 | 778 | 687 | 341 | 116 | 22 | 0 | 0 | 37.3 (%) |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3294 | 1021 | 964 | 862 | 807 | 674 | 646 | 332 | 132 | 28 | 0 | 0 | 36.9 (%) |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3328 | 1032 | 959 | 892 | 771 | 651 | 627 | 335 | 138 | 26 | 1 | 0 | 36.8 (%) |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3288 | 1001 | 937 | 852 | 775 | 646 | 669 | 374 | 172 | 45 | 1 | 0 | 37.2 (%) |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3326 | 1036 | 959 | 896 | 775 | 648 | 624 | 332 | 137 | 26 | 1 | 0 | 36.8 (%) |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3295 | 1027 | 971 | 878 | 810 | 673 | 642 | 310 | 130 | 24 | 0 | 0 | 36.8 (%) |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 5283 | 808 | 642 | 570 | 631 | 461 | 218 | 82 | 58 | 7 | 0 | 0 | 26.2 (%) |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 5727 | 701 | 570 | 615 | 661 | 334 | 120 | 32 | 0 | 0 | 0 | 0 | 23.5 (%) |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 5675 | 718 | 568 | 629 | 689 | 350 | 120 | 11 | 0 | 0 | 0 | 0 | 23.6 (%) |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 5692 | 673 | 486 | 523 | 592 | 426 | 252 | 81 | 35 | 0 | 0 | 0 | 24.0 (%) |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 5734 | 665 | 485 | 541 | 579 | 428 | 227 | 79 | 22 | 0 | 0 | 0 | 23.8 (%) |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 5708 | 673 | 492 | 537 | 587 | 428 | 230 | 82 | 23 | 0 | 0 | 0 | 23.9 (%) |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 5598 | 646 | 546 | 502 | 602 | 460 | 255 | 112 | 34 | 5 | 0 | 0 | 24.3 (%) |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 5338 | 794 | 668 | 622 | 655 | 381 | 203 | 64 | 33 | 2 | 0 | 0 | 25.5 (%) |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 5380 | 780 | 662 | 640 | 639 | 369 | 191 | 66 | 31 | 2 | 0 | 0 | 25.4 (%) |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 5388 | 764 | 682 | 646 | 635 | 383 | 167 | 67 | 27 | 1 | 0 | 0 | 25.3 (%) |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 5323 | 770 | 729 | 612 | 669 | 387 | 180 | 77 | 13 | 0 | 0 | 0 | 25.3 (%) |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 4956 | 860 | 693 | 709 | 837 | 530 | 164 | 11 | 0 | 0 | 0 | 0 | 27.3 (%) |
Zone Overview
| Area (ft^2) | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume (ft^3) | Multiplier | Above Ground Gross Wall Area (ft^2) | Underground Gross Wall Area (ft^2) | Window Glass Area (ft^2) | Lighting (W/ft^2) | People (ft^2/person) | Plug and Process (W/ft^2) | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 1620.08 | Yes | Yes | 17820.49 | 1.00 | 351.98 | 0.0 | 105.7 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1350.01 | Yes | Yes | 12150.01 | 1.00 | 197.95 | 0.0 | 28.2 | 0.66 | 1075.31 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1781.98 | 1.00 | 65.98 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 162.0 | Yes | Yes | 1458.14 | 1.00 | 54.03 | 0.0 | 0.0 | 0.64 | 107.64 | 0.09 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.79 | 107.64 | 0.09 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.91 | 53.82 | 0.09 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 1755.16 | Yes | Yes | 19306.53 | 1.00 | 1012.02 | 0.0 | 159.63 | 1.06 | 107.64 | 0.23 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 15444.16 | 1.00 | 571.99 | 0.0 | 70.83 | 1.11 | 215.06 | 0.7 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 2375.97 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 216.03 | Yes | Yes | 1944.07 | 1.00 | 314.95 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1484.98 | 1.00 | 55.0 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 134.98 | Yes | Yes | 1214.82 | 1.00 | 44.99 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3860.95 | 1.00 | 143.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 360.05 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1134.09 | Yes | Yes | 10206.64 | 1.00 | 378.03 | 0.0 | 72.12 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 1404.15 | Yes | Yes | 12637.0 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3159.25 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 1404.04 | Yes | Yes | 12635.94 | 1.00 | 468.01 | 0.0 | 70.83 | 0.75 | 268.77 | 0.23 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 351.01 | Yes | Yes | 3158.9 | 1.00 | 117.0 | 0.0 | 17.76 | 0.75 | 268.77 | 0.23 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 1053.03 | Yes | Yes | 11582.86 | 1.00 | 429.05 | 0.0 | 53.17 | 0.57 | 1075.31 | 0.09 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 1.24 | 2173.88 | 0.09 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 864.02 | Yes | Yes | 9504.59 | 1.00 | 351.98 | 0.0 | 53.17 | 1.24 | 2173.88 | 0.09 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.43 | 1.00 | 315.06 | 0.0 | 0.0 | 0.69 | 2173.88 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 2376.68 | 1.00 | 385.03 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 216.03 | Yes | Yes | 1944.78 | 1.00 | 315.06 | 0.0 | 0.0 | 0.57 | 1075.31 | 0.09 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 351.01 | Yes | Yes | 3861.31 | 1.00 | 143.05 | 0.0 | 0.0 | 0.88 | 322.59 | 0.09 |
| Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Conditioned Total | 43201.82 | 410417.54 | 18240.31 | 0.0 | 1982.71 | 0.77 | 287.83 | 0.19 | |||
| Unconditioned Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | |||
| Not Part of Total | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| Heating/Cooling | Calculated Design Load | Design Load With Sizing Factor | Calculated Design Air Flow (ft^3/min) | Design Air Flow With Sizing Factor (ft^3/min) | Date/Time Of Peak | Outdoor Temperature at Peak Load (F) | Outdoor Humidity Ratio at Peak Load (lbWater/lbAir) | |
|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.42 (ton) | 0.46 (ton) | 241.55 | 264.86 | 7/21 17:15:00 | 83.37 | 0.01 |
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 10.5 (kBtu/h) | 13.65 (kBtu/h) | 260.62 | 339.02 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.32 (ton) | 0.35 (ton) | 184.34 | 201.29 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 5.93 (kBtu/h) | 7.71 (kBtu/h) | 146.2 | 190.7 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.33 (ton) | 0.36 (ton) | 188.58 | 207.65 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 7.33 (kBtu/h) | 9.52 (kBtu/h) | 182.22 | 237.31 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.52 (ton) | 0.57 (ton) | 298.76 | 328.43 | 7/21 15:30:00 | 86.41 | 0.01 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 18.06 (kBtu/h) | 23.48 (kBtu/h) | 451.32 | 586.93 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 36.02 | 131.37 | 7/21 17:00:00 | 83.93 | 0.01 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | Heating | 1.33 (kBtu/h) | 1.73 (kBtu/h) | 33.9 | 131.37 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 33.9 | 131.37 | 7/21 17:00:00 | 83.93 | 0.01 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | Heating | 0.87 (kBtu/h) | 1.13 (kBtu/h) | 21.19 | 131.37 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 36.02 | 131.37 | 7/21 17:00:00 | 83.93 | 0.01 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | Heating | 1.07 (kBtu/h) | 1.39 (kBtu/h) | 27.55 | 131.37 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 50.85 | 131.37 | 7/21 14:45:00 | 87.08 | 0.01 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | Heating | 2.45 (kBtu/h) | 3.19 (kBtu/h) | 61.45 | 131.37 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.18 (ton) | 0.2 (ton) | 103.83 | 114.42 | 7/21 13:30:00 | 86.52 | 0.01 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 1.98 (kBtu/h) | 2.57 (kBtu/h) | 48.73 | 65.69 | 1/21 10:00:00 | -28.3 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Cooling | 0.24 (ton) | 0.26 (ton) | 137.73 | 300.88 | 7/21 13:15:00 | 86.23 | 0.01 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | Heating | 1.57 (kBtu/h) | 2.04 (kBtu/h) | 38.14 | 300.88 | 1/21 10:00:00 | -28.3 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Cooling | 0.85 (ton) | 0.93 (ton) | 489.46 | 538.2 | 7/21 15:00:00 | 87.08 | 0.01 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | Heating | 4.46 (kBtu/h) | 5.79 (kBtu/h) | 110.18 | 500.06 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Cooling | 0.78 (ton) | 0.86 (ton) | 453.44 | 497.94 | 7/21 15:00:00 | 87.08 | 0.01 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | Heating | 7.81 (kBtu/h) | 10.15 (kBtu/h) | 192.82 | 252.15 | 1/21 08:00:00 | -28.3 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Cooling | 0.04 (ton) | 0.04 (ton) | 23.31 | 25.43 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | Heating | 3.4 (kBtu/h) | 4.42 (kBtu/h) | 84.76 | 110.18 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 23.31 | 27.55 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 2.99 (kBtu/h) | 3.89 (kBtu/h) | 74.16 | 97.47 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 3.25 (kBtu/h) | 4.22 (kBtu/h) | 80.52 | 105.94 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.07 (ton) | 0.08 (ton) | 42.38 | 46.62 | 7/21 15:00:00 | 87.08 | 0.01 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 4.78 (kBtu/h) | 6.21 (kBtu/h) | 120.78 | 156.8 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 16:00:00 | 85.73 | 0.01 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 1.35 (kBtu/h) | 1.76 (kBtu/h) | 33.9 | 44.5 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 19.07 | 21.19 | 7/21 16:00:00 | 85.73 | 0.01 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | Heating | 1.11 (kBtu/h) | 1.45 (kBtu/h) | 27.55 | 36.02 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.03 (ton) | 0.04 (ton) | 21.19 | 23.31 | 7/21 16:00:00 | 85.73 | 0.01 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | Heating | 1.27 (kBtu/h) | 1.65 (kBtu/h) | 31.78 | 40.26 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 38.14 | 7/21 14:15:00 | 87.08 | 0.01 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | Heating | 2.35 (kBtu/h) | 3.06 (kBtu/h) | 59.33 | 76.28 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 2.02 (kBtu/h) | 2.62 (kBtu/h) | 50.85 | 65.69 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 2.11 (kBtu/h) | 2.75 (kBtu/h) | 52.97 | 67.8 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 48.73 | 52.97 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 2.45 (kBtu/h) | 3.18 (kBtu/h) | 61.45 | 78.4 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 52.97 | 59.33 | 7/21 13:45:00 | 86.79 | 0.01 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 2.32 (kBtu/h) | 3.02 (kBtu/h) | 57.21 | 74.16 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 14:00:00 | 87.08 | 0.01 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | Heating | 2.24 (kBtu/h) | 2.91 (kBtu/h) | 55.09 | 72.04 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 67.8 | 74.16 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | Heating | 3.41 (kBtu/h) | 4.44 (kBtu/h) | 84.76 | 110.18 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.4 (ton) | 0.44 (ton) | 230.96 | 252.15 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 5.75 (kBtu/h) | 7.48 (kBtu/h) | 141.96 | 184.34 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.29 (ton) | 0.32 (ton) | 167.39 | 184.34 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 5.15 (kBtu/h) | 6.69 (kBtu/h) | 127.13 | 165.27 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.34 (ton) | 0.38 (ton) | 197.06 | 218.24 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 5.86 (kBtu/h) | 7.62 (kBtu/h) | 144.08 | 188.58 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 52.97 | 59.33 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | Heating | 2.02 (kBtu/h) | 2.62 (kBtu/h) | 50.85 | 65.69 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 59.33 | 63.57 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.88 (kBtu/h) | 2.44 (kBtu/h) | 46.62 | 61.45 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.39 (ton) | 0.43 (ton) | 228.84 | 250.03 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 6.15 (kBtu/h) | 8.0 (kBtu/h) | 152.56 | 199.17 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.8 (kBtu/h) | 2.35 (kBtu/h) | 44.5 | 59.33 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.42 (ton) | 0.46 (ton) | 239.43 | 264.86 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 5.86 (kBtu/h) | 7.62 (kBtu/h) | 146.2 | 188.58 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 65.69 | 72.04 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | Heating | 1.77 (kBtu/h) | 2.31 (kBtu/h) | 44.5 | 57.21 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | Heating | 4.04 (kBtu/h) | 5.25 (kBtu/h) | 101.71 | 131.37 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.38 (ton) | 0.42 (ton) | 218.24 | 241.55 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 7.42 (kBtu/h) | 9.64 (kBtu/h) | 184.34 | 239.43 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.31 (ton) | 0.34 (ton) | 177.99 | 197.06 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 6.46 (kBtu/h) | 8.4 (kBtu/h) | 161.03 | 209.77 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.37 (ton) | 0.4 (ton) | 211.89 | 233.08 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 7.37 (kBtu/h) | 9.58 (kBtu/h) | 182.22 | 237.31 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Cooling | 0.1 (ton) | 0.11 (ton) | 57.21 | 61.45 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | Heating | 2.38 (kBtu/h) | 3.09 (kBtu/h) | 59.33 | 76.28 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.24 (kBtu/h) | 2.91 (kBtu/h) | 55.09 | 72.04 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.41 (ton) | 0.45 (ton) | 239.43 | 262.74 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 7.36 (kBtu/h) | 9.57 (kBtu/h) | 182.22 | 237.31 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.05 (kBtu/h) | 2.67 (kBtu/h) | 50.85 | 65.69 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.41 (ton) | 0.46 (ton) | 239.43 | 262.74 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 7.21 (kBtu/h) | 9.38 (kBtu/h) | 180.1 | 233.08 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.11 (ton) | 0.12 (ton) | 61.45 | 67.8 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | Heating | 2.12 (kBtu/h) | 2.76 (kBtu/h) | 52.97 | 67.8 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Cooling | 0.14 (ton) | 0.15 (ton) | 80.52 | 88.99 | 7/21 14:30:00 | 87.08 | 0.01 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | Heating | 6.4 (kBtu/h) | 8.32 (kBtu/h) | 161.03 | 207.65 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.46 (ton) | 0.5 (ton) | 264.86 | 290.29 | 7/21 14:15:00 | 87.08 | 0.01 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 16.28 (kBtu/h) | 21.16 (kBtu/h) | 406.82 | 529.72 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.39 (ton) | 0.43 (ton) | 224.6 | 247.91 | 7/21 14:15:00 | 87.08 | 0.01 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 13.63 (kBtu/h) | 17.72 (kBtu/h) | 341.14 | 442.85 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.45 (ton) | 0.5 (ton) | 262.74 | 288.17 | 7/21 14:15:00 | 87.08 | 0.01 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 16.21 (kBtu/h) | 21.07 (kBtu/h) | 404.71 | 527.6 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Cooling | 0.12 (ton) | 0.13 (ton) | 69.92 | 76.28 | 7/21 14:30:00 | 87.08 | 0.01 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | Heating | 4.77 (kBtu/h) | 6.2 (kBtu/h) | 118.66 | 154.68 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.17 (ton) | 0.19 (ton) | 97.47 | 108.06 | 7/21 13:45:00 | 86.79 | 0.01 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 4.71 (kBtu/h) | 6.12 (kBtu/h) | 118.66 | 152.56 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.66 (ton) | 0.73 (ton) | 381.4 | 419.54 | 7/21 13:45:00 | 86.79 | 0.01 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 16.17 (kBtu/h) | 21.02 (kBtu/h) | 404.71 | 525.48 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.17 (ton) | 0.19 (ton) | 99.59 | 108.06 | 7/21 13:45:00 | 86.79 | 0.01 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 4.59 (kBtu/h) | 5.97 (kBtu/h) | 114.42 | 148.32 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.65 (ton) | 0.72 (ton) | 377.16 | 415.3 | 7/21 13:45:00 | 86.79 | 0.01 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 16.11 (kBtu/h) | 20.95 (kBtu/h) | 402.59 | 523.36 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Cooling | 0.17 (ton) | 0.19 (ton) | 97.47 | 108.06 | 7/21 13:45:00 | 86.79 | 0.01 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | Heating | 4.62 (kBtu/h) | 6.01 (kBtu/h) | 116.54 | 150.44 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Cooling | 0.34 (ton) | 0.37 (ton) | 194.94 | 214.01 | 7/21 13:45:00 | 86.79 | 0.01 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | Heating | 7.24 (kBtu/h) | 9.42 (kBtu/h) | 180.1 | 233.08 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 50.85 | 55.09 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.73 (kBtu/h) | 2.25 (kBtu/h) | 42.38 | 55.09 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.2 (ton) | 0.22 (ton) | 114.42 | 127.13 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 4.76 (kBtu/h) | 6.19 (kBtu/h) | 118.66 | 152.56 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Cooling | 0.04 (ton) | 0.05 (ton) | 25.43 | 27.55 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | Heating | 3.35 (kBtu/h) | 4.36 (kBtu/h) | 84.76 | 108.06 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 25.43 | 29.66 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | Heating | 2.95 (kBtu/h) | 3.83 (kBtu/h) | 74.16 | 95.35 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.05 (ton) | 27.55 | 29.66 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | Heating | 3.21 (kBtu/h) | 4.17 (kBtu/h) | 80.52 | 103.83 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Cooling | 0.08 (ton) | 0.09 (ton) | 44.5 | 48.73 | 7/21 14:30:00 | 87.08 | 0.01 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | Heating | 4.77 (kBtu/h) | 6.2 (kBtu/h) | 118.66 | 154.68 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Cooling | 0.05 (ton) | 0.06 (ton) | 29.66 | 31.78 | 7/21 16:00:00 | 85.73 | 0.01 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | Heating | 3.69 (kBtu/h) | 4.79 (kBtu/h) | 93.23 | 120.78 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.06 (ton) | 31.78 | 36.02 | 7/21 16:00:00 | 85.73 | 0.01 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | Heating | 3.34 (kBtu/h) | 4.34 (kBtu/h) | 82.64 | 108.06 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Cooling | 0.06 (ton) | 0.07 (ton) | 33.9 | 38.14 | 7/21 16:00:00 | 85.73 | 0.01 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | Heating | 3.61 (kBtu/h) | 4.69 (kBtu/h) | 91.11 | 116.54 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 55.09 | 59.33 | 7/21 14:15:00 | 87.08 | 0.01 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | Heating | 4.95 (kBtu/h) | 6.44 (kBtu/h) | 125.01 | 161.03 | 1/21 09:00:00 | -28.3 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Cooling | 0.09 (ton) | 0.1 (ton) | 50.85 | 57.21 | 7/21 22:00:00 | 71.78 | 0.01 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | Heating | 1.6 (kBtu/h) | 2.08 (kBtu/h) | 40.26 | 50.85 | 1/21 09:00:00 | -28.3 | 0.0 |
Zone Equipment Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric | ||||||
| OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
| OS:ZoneHVAC:Baseboard:Convective:Electric |
Air Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.36 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 68.0 to 68.0 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 32,185 | ft^2 | 42 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 42 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Make-up air unit Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | DifferentialEnthalpy | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-CorridorFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,620 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr1 Sys-3 Flr-2 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr2 Sys-3 Flr-1 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr3 Sys-3 Flr-4 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-ElevatorCoreFlr4 Sys-3 Flr-3 Sch-C HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 162 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-EmployeeLoungeFlr1 Sys-3 Flr-2 Sch-B HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontLoungeFlr1 Sys-3 Flr-2 Sch-H HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr1 Sys-4 Flr-2 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr2 Sys-4 Flr-1 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr3 Sys-4 Flr-4 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStairsFlr4 Sys-4 Flr-3 Sch-F HPlcmt-east ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-FrontStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 135 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-LaundryRoomFlr1 Sys-4 Flr-2 Sch-E HPlcmt-south ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,053 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MechanicalRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-MeetingRoomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 864 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr1 Sys-4 Flr-2 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr2 Sys-4 Flr-1 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr3 Sys-4 Flr-4 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RearStorageFlr4 Sys-4 Flr-3 Sch-E HPlcmt-west ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 216 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:DX:SingleSpeed | Autosized | Btu/h | Rated COP | 3.82 | COP | |
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:ConstantVolume | Autosized | cfm | Pressure Rise | 2.57 | inH_{2}O | |
| OS:SetpointManager:SingleZone:Reheat | Control Zone | Sp-RestroomFlr1 Sys-3 Flr-2 Sch-F HPlcmt-north ZN | ||||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 351 | ft^2 | 1 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 75.2 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:Uncontrolled | 1 | ||||
(controls) |
||||||
| HVAC Operation Schedule | Always On Discrete | |||||
| Night Cycle Setting | StayOff | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:AirLoopHVAC:OutdoorAirSystem | Autosized | cfm | Minimum Outdoor Air Flow Rate | 0.00 | cfm | |
| OS:Coil:Cooling:Water | Autosized | gal/min | Plant Loop | Chilled Water Loop | ||
| OS:Coil:Heating:Electric | Autosized | Btu/h | Efficiency | 1.00 | ||
| OS:Fan:VariableVolume | Autosized | cfm | Pressure Rise | 5.85 | inH_{2}O | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 55.4 to 55.4 | F | |||
(demand) |
||||||
| Thermal Zones | Total Floor Area | 1,755 | ft^2 | 2 | ||
| Thermal Zones | thermostat ranges for cooling | 75.2 to 95.0 | F | |||
| Thermal Zones | thermostat ranges for heating | 64.4 to 71.6 | F | |||
| Terminal Types Used | OS:AirTerminal:SingleDuct:VAV:Reheat | 2 | ||||
(controls) |
||||||
| HVAC Operation Schedule | VAV with Reheat Occ Sch | |||||
| Night Cycle Setting | CycleOnAny | Choice | ||||
| Economizer Setting | NoEconomizer | Choice | ||||
| Demand Controlled Ventilation Status | false | Bool |
Plant Loops Detail
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:Chiller:Electric:EIR | 30,999.00 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 44.6 to 44.6 | F | |||
| OS:Chiller:Electric:EIR | 0.00 | Btu/h | Reference COP | 4.50 | ||
| OS:Chiller:Electric:EIR (cont) | Chiller Source | Condenser Water Loop | ||||
(demand) |
||||||
| OS:Coil:Cooling:Water | Air Loop | VAV with Reheat | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 44.60 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:CoolingTower:SingleSpeed - Air | Autosized | gal/min | ||||
| OS:CoolingTower:SingleSpeed (cont) - Water | Autosized | cfm | Fan Power at Design Air Flow Rate | 352,868.07 | W | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 84.2 to 84.2 | F | |||
(demand) |
||||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
| OS:Chiller:Electric:EIR | Plant Loop | Chilled Water Loop | ||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 32.0 to 212.0 | F | ||||
| Design Loop Exit Temperature | 84.20 | F | ||||
| Loop Design Temperature Difference | 10.80 | R |
| Object | Sizing | Sizing Units | Description | Value | Value Units | Count |
|---|---|---|---|---|---|---|
(supply) |
||||||
| OS:Pump:ConstantSpeed | Autosized | gal/min | Rated Power Consumption | Autosized | W | |
| OS:WaterHeater:Mixed | 300 | gal | Heater Thermal Efficiency | 1.00 | fraction | |
| OS:SetpointManager:Scheduled | Control Variable - Temperature | 140.0 to 140.0 | F | |||
(demand) |
||||||
| OS:WaterUse:Connections | Water Use Connections 1 | |||||
| OS:WaterUse:Connections | Water Use Connections 2 | |||||
| OS:WaterUse:Connections | Water Use Connections 3 | |||||
| OS:WaterUse:Connections | Water Use Connections 4 | |||||
| OS:WaterUse:Connections | Water Use Connections 5 | |||||
| OS:WaterUse:Connections | Water Use Connections 6 | |||||
| OS:WaterUse:Connections | Water Use Connections 7 | |||||
| OS:WaterUse:Connections | Water Use Connections 8 | |||||
| OS:WaterUse:Connections | Water Use Connections 9 | |||||
| OS:WaterUse:Connections | Water Use Connections 10 | |||||
| OS:WaterUse:Connections | Water Use Connections 11 | |||||
| OS:WaterUse:Connections | Water Use Connections 12 | |||||
| OS:WaterUse:Connections | Water Use Connections 13 | |||||
| OS:WaterUse:Connections | Water Use Connections 14 | |||||
| OS:WaterUse:Connections | Water Use Connections 15 | |||||
| OS:WaterUse:Connections | Water Use Connections 16 | |||||
| OS:WaterUse:Connections | Water Use Connections 17 | |||||
| OS:WaterUse:Connections | Water Use Connections 18 | |||||
| OS:WaterUse:Connections | Water Use Connections 19 | |||||
| OS:WaterUse:Connections | Water Use Connections 20 | |||||
| OS:WaterUse:Connections | Water Use Connections 21 | |||||
| OS:WaterUse:Connections | Water Use Connections 22 | |||||
| OS:WaterUse:Connections | Water Use Connections 23 | |||||
| OS:WaterUse:Connections | Water Use Connections 24 | |||||
| OS:WaterUse:Connections | Water Use Connections 25 | |||||
| OS:WaterUse:Connections | Water Use Connections 26 | |||||
| OS:WaterUse:Connections | Water Use Connections 27 | |||||
| OS:WaterUse:Connections | Water Use Connections 28 | |||||
| OS:WaterUse:Connections | Water Use Connections 29 | |||||
| OS:WaterUse:Connections | Water Use Connections 30 | |||||
| OS:WaterUse:Connections | Water Use Connections 31 | |||||
| OS:WaterUse:Connections | Water Use Connections 32 | |||||
| OS:WaterUse:Connections | Water Use Connections 33 | |||||
| OS:WaterUse:Connections | Water Use Connections 34 | |||||
| OS:WaterUse:Connections | Water Use Connections 35 | |||||
| OS:WaterUse:Connections | Water Use Connections 36 | |||||
| OS:WaterUse:Connections | Water Use Connections 37 | |||||
| OS:WaterUse:Connections | Water Use Connections 38 | |||||
| OS:WaterUse:Connections | Water Use Connections 39 | |||||
| OS:WaterUse:Connections | Water Use Connections 40 | |||||
| OS:WaterUse:Connections | Water Use Connections 41 | |||||
| OS:WaterUse:Connections | Water Use Connections 42 | |||||
| OS:WaterUse:Connections | Water Use Connections 43 | |||||
| OS:WaterUse:Connections | Water Use Connections 44 | |||||
| OS:WaterUse:Connections | Water Use Connections 45 | |||||
| OS:WaterUse:Connections | Water Use Connections 46 | |||||
| OS:WaterUse:Connections | Water Use Connections 47 | |||||
| OS:WaterUse:Connections | Water Use Connections 48 | |||||
(controls) |
||||||
| Loop Flow Rate Range | Autosized | gal/min | Minimum Loop Flow Rate | 0.0 | gal/min | |
| Loop Temperature Range | 50.0 to 140.0 | F | ||||
| Design Loop Exit Temperature | 140.00 | F | ||||
| Loop Design Temperature Difference | 9.00 | R |
Outdoor Air
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume (ft^3) | Avg. Mechanical Ventilation (ach) | Min. Mechanical Ventilation (ach) | Avg. Infiltration (ach) | Min. Infiltration (ach) | Avg. Simple Ventilation (ach) | Min. Simple Ventilation (ach) | |
|---|---|---|---|---|---|---|---|---|---|
| SP-CORRIDORFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.86 | 1.51 | 17820 | 0.332 | 0.319 | 0.031 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR2 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.449 | 0.392 | 0.032 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR3 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.443 | 0.392 | 0.036 | 0.0 | 0.0 | 0.0 |
| SP-CORRIDORFLR4 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.72 | 1.26 | 12150 | 0.42 | 0.389 | 0.298 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR1 SYS-3 FLR-2 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1782 | 4.481 | 4.348 | 0.064 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR2 SYS-3 FLR-1 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.477 | 5.313 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR3 SYS-3 FLR-4 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.477 | 5.313 | 0.089 | 0.0 | 0.0 | 0.0 |
| SP-ELEVATORCOREFLR4 SYS-3 FLR-3 SCH-C HPLCMT-SOUTH ZN | 0.75 | 1.5 | 1458 | 5.477 | 5.314 | 0.382 | 0.0 | 0.0 | 0.0 |
| SP-EMPLOYEELOUNGEFLR1 SYS-3 FLR-2 SCH-B HPLCMT-SOUTH ZN | 1.56 | 3.26 | 3861 | 1.026 | 0.991 | 0.061 | 0.0 | 0.0 | 0.0 |
| SP-EXERCISECENTERFLR1 SYS-6 FLR-2 SCH-B HPLCMT-SOUTH ZN | 3.12 | 6.52 | 3861 | 1.174 | 0.0 | 0.061 | 0.0 | 0.0 | 0.0 |
| SP-FRONTLOUNGEFLR1 SYS-3 FLR-2 SCH-H HPLCMT-NORTH ZN | 14.67 | 16.31 | 19307 | 1.578 | 1.514 | 0.082 | 0.0 | 0.0 | 0.0 |
| SP-FRONTOFFICEFLR1 SYS-6 FLR-2 SCH-A HPLCMT-SOUTH ZN | 3.51 | 6.53 | 15444 | 0.759 | 0.0 | 0.062 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR1 SYS-4 FLR-2 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 2376 | 0.331 | 0.318 | 0.255 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR2 SYS-4 FLR-1 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.389 | 0.32 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR3 SYS-4 FLR-4 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.389 | 0.354 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTAIRSFLR4 SYS-4 FLR-3 SCH-F HPLCMT-EAST ZN | 0.06 | 0.1 | 1944 | 0.405 | 0.389 | 0.639 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1485 | 0.388 | 0.375 | 0.066 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.474 | 0.458 | 0.083 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.474 | 0.459 | 0.092 | 0.0 | 0.0 | 0.0 |
| SP-FRONTSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-SOUTH ZN | 0.08 | 0.13 | 1215 | 0.474 | 0.459 | 0.394 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM101 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.673 | 0.587 | 0.058 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM102 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.67 | 0.587 | 0.058 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM103 SYS-1 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3861 | 0.659 | 0.587 | 0.058 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM104 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.673 | 0.588 | 0.058 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM105 SYS-1 FLR-2 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3861 | 0.686 | 0.588 | 0.058 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM201 SYS-1 FLR-1 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.816 | 0.714 | 0.225 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM202_205 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.864 | 0.718 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM206_208 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.854 | 0.718 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM209_212 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.851 | 0.718 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM213 SYS-1 FLR-1 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.839 | 0.718 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM214 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.876 | 0.719 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM215_218 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.877 | 0.719 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM219 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.851 | 0.719 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM220_223 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.887 | 0.719 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM224 SYS-1 FLR-1 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.883 | 0.719 | 0.073 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM301 SYS-1 FLR-4 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.794 | 0.714 | 0.249 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM302_305 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.852 | 0.717 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM306_308 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.846 | 0.717 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM309_312 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.848 | 0.717 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM313 SYS-1 FLR-4 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.829 | 0.717 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM314 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.865 | 0.719 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM315_318 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.881 | 0.719 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM319 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.85 | 0.719 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM320_323 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.884 | 0.719 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM324 SYS-1 FLR-4 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.877 | 0.719 | 0.081 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM401 SYS-1 FLR-3 SCH-F HPLCMT-EAST ZN | 0.75 | 1.31 | 3159 | 0.77 | 0.713 | 0.526 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM402_405 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.783 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM406_408 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 2.42 | 4.22 | 10207 | 0.784 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM409_412 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 3.0 | 5.22 | 12637 | 0.783 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM413 SYS-1 FLR-3 SCH-F HPLCMT-NORTH ZN | 0.75 | 1.31 | 3159 | 0.779 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM414 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.794 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM415_418 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.804 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM419 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.79 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM420_423 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 3.0 | 5.22 | 12636 | 0.804 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-GUESTROOM424 SYS-1 FLR-3 SCH-F HPLCMT-SOUTH ZN | 0.75 | 1.31 | 3159 | 0.797 | 0.714 | 0.347 | 0.0 | 0.0 | 0.0 |
| SP-LAUNDRYROOMFLR1 SYS-4 FLR-2 SCH-E HPLCMT-SOUTH ZN | 0.62 | 0.98 | 11583 | 0.388 | 0.375 | 0.066 | 0.0 | 0.0 | 0.0 |
| SP-MECHANICALROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.09 | 0.16 | 3861 | 0.332 | 0.319 | 0.058 | 0.0 | 0.0 | 0.0 |
| SP-MEETINGROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.23 | 0.4 | 9505 | 0.331 | 0.318 | 0.058 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR1 SYS-1 FLR-2 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 2377 | 0.338 | 0.319 | 0.255 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR2 SYS-1 FLR-1 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.414 | 0.389 | 0.32 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR3 SYS-1 FLR-4 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.415 | 0.389 | 0.354 | 0.0 | 0.0 | 0.0 |
| SP-REARSTAIRSFLR4 SYS-1 FLR-3 SCH-F HPLCMT-WEST ZN | 0.06 | 0.1 | 1944 | 0.442 | 0.389 | 0.639 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR1 SYS-4 FLR-2 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 2377 | 0.388 | 0.376 | 0.29 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR2 SYS-4 FLR-1 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.459 | 0.364 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR3 SYS-4 FLR-4 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.459 | 0.402 | 0.0 | 0.0 | 0.0 |
| SP-REARSTORAGEFLR4 SYS-4 FLR-3 SCH-E HPLCMT-WEST ZN | 0.13 | 0.2 | 1945 | 0.474 | 0.459 | 0.727 | 0.0 | 0.0 | 0.0 |
| SP-RESTROOMFLR1 SYS-3 FLR-2 SCH-F HPLCMT-NORTH ZN | 0.62 | 1.09 | 3861 | 0.332 | 0.319 | 0.058 | 0.0 | 0.0 | 0.0 |
Cash Flow
No Data to Show for Cash Flow
Site and Source Summary
| Total Energy (kBtu) | Energy Per Total Building Area (kBtu/ft^2) | Energy Per Conditioned Building Area (kBtu/ft^2) | |
|---|---|---|---|
| Total Site Energy | 3240890.1 | 75.0 | 75.0 |
| Net Site Energy | 3240890.1 | 75.0 | 75.0 |
| Total Source Energy | 10263882.9 | 237.6 | 237.6 |
| Net Source Energy | 10263882.9 | 237.6 | 237.6 |
| Site=>Source Conversion Factor | |
|---|---|
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
Schedule Overview
| Schedule | Type Limits | Rules | Use Count |
|---|---|---|---|
| Air Velocity Schedule | Velocity | 0 | 11 |
| Always On | Dimensionless | 0 | 67 |
| CHW Temp | Temperature | 3 | 1 |
| Clothing Schedule | ClothingInsulation | 1 | 11 |
| CW Temp | Temperature | 3 | 1 |
| Make-up air unit Occ Sch | Dimensionless | 7 | 2 |
| Makeup-Air Unit Supply Air Temp | Temperature | 0 | 1 |
| NECB-A-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-A-Lighting | Dimensionless | 3 | 1 |
| NECB-A-Occupancy | Dimensionless | 3 | 1 |
| NECB-A-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-A-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-A-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| NECB-Activity | ActivityLevel | 0 | 67 |
| NECB-B-Electric-Equipment | Dimensionless | 3 | 2 |
| NECB-B-Lighting | Dimensionless | 3 | 2 |
| NECB-B-Occupancy | Dimensionless | 3 | 2 |
| NECB-B-Service Water Heating | Dimensionless | 3 | 2 |
| NECB-B-Thermostat Setpoint-Cooling | Temperature | 3 | 6 |
| NECB-B-Thermostat Setpoint-Heating | Temperature | 3 | 6 |
| NECB-C-Electric-Equipment | Dimensionless | 3 | 4 |
| NECB-C-Lighting | Dimensionless | 3 | 4 |
| NECB-C-Occupancy | Dimensionless | 3 | 4 |
| NECB-C-Thermostat Setpoint-Cooling | Temperature | 3 | 9 |
| NECB-C-Thermostat Setpoint-Heating | Temperature | 3 | 9 |
| NECB-E-Electric-Equipment | Dimensionless | 3 | 9 |
| NECB-E-Lighting | Dimensionless | 3 | 9 |
| NECB-E-Occupancy | Dimensionless | 3 | 9 |
| NECB-E-Service Water Heating | Dimensionless | 3 | 9 |
| NECB-E-Thermostat Setpoint-Cooling | Temperature | 3 | 19 |
| NECB-E-Thermostat Setpoint-Heating | Temperature | 3 | 19 |
| NECB-F-Electric-Equipment | Dimensionless | 3 | 50 |
| NECB-F-Lighting | Dimensionless | 3 | 50 |
| NECB-F-Occupancy | Dimensionless | 3 | 50 |
| NECB-F-Service Water Heating | Dimensionless | 3 | 35 |
| NECB-F-Thermostat Setpoint-Cooling | Temperature | 3 | 105 |
| NECB-F-Thermostat Setpoint-Heating | Temperature | 3 | 105 |
| NECB-H-Electric-Equipment | Dimensionless | 3 | 1 |
| NECB-H-Lighting | Dimensionless | 3 | 1 |
| NECB-H-Occupancy | Dimensionless | 3 | 1 |
| NECB-H-Service Water Heating | Dimensionless | 3 | 1 |
| NECB-H-Thermostat Setpoint-Cooling | Temperature | 3 | 3 |
| NECB-H-Thermostat Setpoint-Heating | Temperature | 3 | 3 |
| ON_OFF_ALWAYS_OFF | Availability | 3 | 42 |
| Schedule Ruleset 10 | 0 | 1 | |
| Schedule Ruleset 100 | 0 | 1 | |
| Schedule Ruleset 101 | 0 | 1 | |
| Schedule Ruleset 102 | 0 | 1 | |
| Schedule Ruleset 103 | 0 | 1 | |
| Schedule Ruleset 104 | 0 | 1 | |
| Schedule Ruleset 105 | 0 | 1 | |
| Schedule Ruleset 106 | 0 | 1 | |
| Schedule Ruleset 107 | 0 | 1 | |
| Schedule Ruleset 108 | 0 | 1 | |
| Schedule Ruleset 109 | 0 | 1 | |
| Schedule Ruleset 11 | 0 | 1 | |
| Schedule Ruleset 110 | 0 | 1 | |
| Schedule Ruleset 111 | 0 | 1 | |
| Schedule Ruleset 112 | 0 | 1 | |
| Schedule Ruleset 113 | 0 | 1 | |
| Schedule Ruleset 114 | 0 | 1 | |
| Schedule Ruleset 115 | 0 | 1 | |
| Schedule Ruleset 116 | 0 | 1 | |
| Schedule Ruleset 117 | 0 | 1 | |
| Schedule Ruleset 118 | 0 | 1 | |
| Schedule Ruleset 119 | 0 | 1 | |
| Schedule Ruleset 12 | 0 | 1 | |
| Schedule Ruleset 120 | 0 | 1 | |
| Schedule Ruleset 121 | 0 | 1 | |
| Schedule Ruleset 122 | 0 | 1 | |
| Schedule Ruleset 123 | 0 | 1 | |
| Schedule Ruleset 124 | 0 | 1 | |
| Schedule Ruleset 125 | 0 | 1 | |
| Schedule Ruleset 126 | 0 | 1 | |
| Schedule Ruleset 127 | 0 | 1 | |
| Schedule Ruleset 128 | 0 | 1 | |
| Schedule Ruleset 129 | 0 | 1 | |
| Schedule Ruleset 13 | 0 | 1 | |
| Schedule Ruleset 130 | 0 | 1 | |
| Schedule Ruleset 131 | 0 | 1 | |
| Schedule Ruleset 132 | 0 | 1 | |
| Schedule Ruleset 133 | 0 | 1 | |
| Schedule Ruleset 134 | 0 | 1 | |
| Schedule Ruleset 135 | 0 | 1 | |
| Schedule Ruleset 136 | 0 | 1 | |
| Schedule Ruleset 137 | 0 | 1 | |
| Schedule Ruleset 138 | 0 | 1 | |
| Schedule Ruleset 139 | 0 | 1 | |
| Schedule Ruleset 14 | 0 | 1 | |
| Schedule Ruleset 140 | 0 | 1 | |
| Schedule Ruleset 141 | 0 | 1 | |
| Schedule Ruleset 142 | 0 | 1 | |
| Schedule Ruleset 143 | 0 | 1 | |
| Schedule Ruleset 144 | 0 | 1 | |
| Schedule Ruleset 145 | 0 | 1 | |
| Schedule Ruleset 146 | 0 | 1 | |
| Schedule Ruleset 15 | 0 | 1 | |
| Schedule Ruleset 16 | 0 | 1 | |
| Schedule Ruleset 17 | 0 | 1 | |
| Schedule Ruleset 18 | 0 | 1 | |
| Schedule Ruleset 19 | 0 | 1 | |
| Schedule Ruleset 20 | 0 | 1 | |
| Schedule Ruleset 21 | 0 | 1 | |
| Schedule Ruleset 22 | 0 | 1 | |
| Schedule Ruleset 23 | 0 | 1 | |
| Schedule Ruleset 24 | 0 | 1 | |
| Schedule Ruleset 25 | 0 | 1 | |
| Schedule Ruleset 26 | 0 | 1 | |
| Schedule Ruleset 27 | 0 | 1 | |
| Schedule Ruleset 28 | 0 | 1 | |
| Schedule Ruleset 29 | 0 | 1 | |
| Schedule Ruleset 3 | 0 | 1 | |
| Schedule Ruleset 30 | 0 | 1 | |
| Schedule Ruleset 31 | 0 | 1 | |
| Schedule Ruleset 32 | 0 | 1 | |
| Schedule Ruleset 33 | 0 | 1 | |
| Schedule Ruleset 34 | 0 | 1 | |
| Schedule Ruleset 35 | 0 | 1 | |
| Schedule Ruleset 36 | 0 | 1 | |
| Schedule Ruleset 37 | 0 | 1 | |
| Schedule Ruleset 38 | 0 | 1 | |
| Schedule Ruleset 39 | 0 | 1 | |
| Schedule Ruleset 4 | 0 | 1 | |
| Schedule Ruleset 40 | 0 | 1 | |
| Schedule Ruleset 41 | 0 | 1 | |
| Schedule Ruleset 42 | 0 | 1 | |
| Schedule Ruleset 43 | 0 | 1 | |
| Schedule Ruleset 44 | 0 | 1 | |
| Schedule Ruleset 45 | 0 | 1 | |
| Schedule Ruleset 46 | 0 | 1 | |
| Schedule Ruleset 47 | 0 | 1 | |
| Schedule Ruleset 48 | 0 | 1 | |
| Schedule Ruleset 49 | 0 | 1 | |
| Schedule Ruleset 5 | 0 | 1 | |
| Schedule Ruleset 50 | 0 | 1 | |
| Schedule Ruleset 51 | 0 | 1 | |
| Schedule Ruleset 52 | 0 | 1 | |
| Schedule Ruleset 53 | 0 | 1 | |
| Schedule Ruleset 54 | 0 | 1 | |
| Schedule Ruleset 55 | 0 | 1 | |
| Schedule Ruleset 56 | 0 | 1 | |
| Schedule Ruleset 57 | 0 | 1 | |
| Schedule Ruleset 58 | 0 | 1 | |
| Schedule Ruleset 59 | 0 | 1 | |
| Schedule Ruleset 6 | 0 | 1 | |
| Schedule Ruleset 60 | 0 | 1 | |
| Schedule Ruleset 61 | 0 | 1 | |
| Schedule Ruleset 62 | 0 | 1 | |
| Schedule Ruleset 63 | 0 | 1 | |
| Schedule Ruleset 64 | 0 | 1 | |
| Schedule Ruleset 65 | 0 | 1 | |
| Schedule Ruleset 66 | 0 | 1 | |
| Schedule Ruleset 67 | 0 | 1 | |
| Schedule Ruleset 68 | 0 | 1 | |
| Schedule Ruleset 69 | 0 | 1 | |
| Schedule Ruleset 7 | 0 | 1 | |
| Schedule Ruleset 70 | 0 | 1 | |
| Schedule Ruleset 71 | 0 | 1 | |
| Schedule Ruleset 72 | 0 | 1 | |
| Schedule Ruleset 73 | 0 | 1 | |
| Schedule Ruleset 74 | 0 | 1 | |
| Schedule Ruleset 75 | 0 | 1 | |
| Schedule Ruleset 76 | 0 | 1 | |
| Schedule Ruleset 77 | 0 | 1 | |
| Schedule Ruleset 78 | 0 | 1 | |
| Schedule Ruleset 79 | 0 | 1 | |
| Schedule Ruleset 8 | 0 | 1 | |
| Schedule Ruleset 80 | 0 | 1 | |
| Schedule Ruleset 81 | 0 | 1 | |
| Schedule Ruleset 82 | 0 | 1 | |
| Schedule Ruleset 83 | 0 | 1 | |
| Schedule Ruleset 84 | 0 | 1 | |
| Schedule Ruleset 85 | 0 | 1 | |
| Schedule Ruleset 86 | 0 | 1 | |
| Schedule Ruleset 87 | 0 | 1 | |
| Schedule Ruleset 88 | 0 | 1 | |
| Schedule Ruleset 89 | 0 | 1 | |
| Schedule Ruleset 9 | 0 | 1 | |
| Schedule Ruleset 90 | 0 | 1 | |
| Schedule Ruleset 91 | 0 | 1 | |
| Schedule Ruleset 92 | 0 | 1 | |
| Schedule Ruleset 93 | 0 | 1 | |
| Schedule Ruleset 94 | 0 | 1 | |
| Schedule Ruleset 95 | 0 | 1 | |
| Schedule Ruleset 96 | 0 | 1 | |
| Schedule Ruleset 97 | 0 | 1 | |
| Schedule Ruleset 98 | 0 | 1 | |
| Schedule Ruleset 99 | 0 | 1 | |
| Service Water Loop Temp - 140F | Temperature | 0 | 2 |
| Supply Air Temp | Temperature | 0 | 1 |
| VAV with Reheat Occ Sch | Dimensionless | 7 | 2 |
| Water Heater Ambient Temp Schedule - 70F | Temperature | 0 | 1 |
| Work Efficiency Schedule | Dimensionless | 0 | 11 |